The regular inspection of fire alarm systems is important and crucial to ensure that they function properly in the event of a fire - and thus th
The inspection of fire alarm systems (FAS) is divided into different areas and intervals. The responsibility for compliance with the various testing intervals according to DIN 14675 "Specifications for the installation and operation of fire alarm systems" and DIN VDE 0833 "Specifications for hazard alarm systems for fire, burglary and hold-up" lies with the building operator.
An inspection of the fire alarm system in accordance with DIN 14675 and DIN VDE 0833 is required once every quarter. The following is checked as part of this:
In addition, a visual inspection of fire alarm systems by an instructed person is mandatory every 3 months.
The annual fire alarm system inspection in accordance with DIN 14675 by an expert includes, among other things, the inspection of:
Good to know: For the fire alarm system test, the main detector is switched off so that no alarm is issued to the emergency services.
In addition, the recurring inspection by an external inspection expert is required at least every 3 years according to the TPrüfV (Technical Inspection Ordinance). If the required expert inspection of the fire alarm system has not been carried out, a fine (in accordance with the state building regulations) and the loss of insurance cover in the event of damage may be imposed.
Important: The results of all fire alarm system tests must be documented in an operating log. If this is not done, it is also an administrative offence.
In addition to the above fire alarm system inspections, further measures are prescribed. These include replacing the battery emergency power supply at least every 4 years.
In addition, the fire detectors must be replaced every 5 to 8 years.
Further information on detector replacement according to DIN 14675 can be found here.
CWS Fire Safety GmbH is a certified specialist company according to DIN & VdS for the inspection of fire alarm systems.
Our service technicians will be happy to carry out periodic inspections of your fire alarm systems from various manufacturers (e.g. Hekatron, Esse or Securiton) - nationwide! Request an appointment now.
Important: After a successful fire alarm system test, we will directly hand over the test certificate to you so that you fulfil all DIN requirements. It goes without saying that the system is also properly documented in the operating log.